Commercial and industrial facilities use three-phase alternating current (AC). For a balanced three-phase system, active power in kilowatts is calculated using line-to-line voltage ($V_L$), line current ($I_L$), and power factor ($\cos \varphi$):
Where √3 ≈ 1.73205. Once active power in kW is determined, cumulative energy over time follows the fundamental rule: Energy (kWh) = P (kW) × Time (hours).
A three-phase supply carries three alternating currents, each offset by 120 degrees. At any instant, at least one phase is near its peak, so the total power delivered stays almost constant instead of pulsing the way single-phase power does. That steady delivery is why factories, large motors, and commercial buildings run on three phases: more power through thinner cables, and far less vibration in rotating machines.
The √3 (1.732) in the formula comes from the gap between line-to-line voltage and phase voltage. On a 400V three-phase system, each phase sits at about 230V to neutral, and 400 ÷ 230 ≈ 1.732. Multiply line voltage by line current alone and you understate the power; the √3 corrects for all three phases working together. Power factor matters just as much: a motor running at 0.8 power factor draws more current for the same kilowatts, so two machines with identical amp readings can use quite different amounts of energy.
To estimate a three-phase bill, work phase by phase only if the load is unbalanced. For balanced loads, take one reading of line voltage and line current, apply the formula once, then multiply the kilowatts by running hours to get kWh — the same power × time rule as any single-phase calculation.
Founder & Lead Renewable Energy Specialist
Abdul Rehman is a Renewable Energy Consultant and Solar Systems Specialist. He built kwtokwh.com to provide transparent, accessible calculation tools that help homeowners, electricians, and facility engineers accurately convert electrical power (kW) into billed energy consumption (kWh) calibrated against NIST and IEC metrology standards.